ELIS C

Flowair


Color:
SIZE:
VERSION:


Short characteristic:

ELiS C air curtains ensure thermal protection of a room. It prevents the inflow of cold air during the winter and the inflow of warm air into the air-conditioned rooms during the summer.

Fans made of light, durable plastic ensure silent operation of the unit.

Simple control system, operation depending on temperature and door opening using one of three steps of fan.

ELiS C is available in three lengths: 1 m, 1,5 m and 2 m, in two versions: water (with water heat exchanger), electric (with electric heaters) in white colour (RAL 9016).

Purpose:

ELiS C air curtains are dedicated for public buildings like markets, sports halls, stores, restaurants, etc. ELiS C air curtains are designed for horizontal installation directly above door openings, which height does not exceed 3 m.

Control system:

Basic control is ensured by built-in connection terminal. Additionally, for version with electric heaters, curtain is equipped with control system ensuring cool down of the heaters after turn off of the unit.

Technology / Innovation / Benefits:

Construction of the unit is made of powder-painted steel. It is in standard equipped with bracket for installation on the wall.
 

Specifications of ELIS C
Sku
ELIS-C


Technical data ELiS C 100

ELiS C-W-100 ELiS C-E-100
Power supply [V/Hz] 230 / 50 3 x400 / 50
Power consumption [kW]  0,14 6,5
Current consumption [A] 0,65 9,4
IP 21 21
Insulation class F F
Connection ["] 3/4” -
Air flow [m3/h] 1400 1300
Acoustic pressure level [dB(A)]*  46,5 46,5
Sound power level [dB]** 57 57
Max heating water temperature [oC] 90 -
Max operating pressure.[MPa] 1,6 -
Weight of unit [kg] 19 14,5

* acoustic pressure level given for optimum installation height, during operation on second step, for the room with average sound absorption, capacity 500 m3, at a distance of 3 m from the unit.
** according to ISO 27327-2.


Technical data ELiS C 150

ELiS C-W-150 ELiS C-E-150
Power supply  [V/Hz] 230 / 50 3 x400 / 50
Power consumption [kW]  0,21 10
Current consumption [A] 0,95 14,5
IP 21 21
Insulation class F F
Connection ["] 3/4” -
Air flow  [m3/h] 2100 1950
Acoustic pressure level  [dB(A)]*  48,5 48,5
Sound power level [dB]** 63 63
Max heating water temperature [oC] 90 -
Max operating pressure [MPa] 1,6 -
Weight of unit [kg] 27,5 19,9

* acoustic pressure level given for optimum installation height, during operation on second step, for the room with average sound absorption, capacity 500 m3, at a distance of 3 m from the unit.
** according to ISO 27327-2.


Technical data ELiS C 200

ELiS C-W-200 ELiS C-E-200
Power supply [V/Hz] 230 / 50 3 x400 / 50
Power consumption [kW]  0,26 13
Current consumption [A] 1,2 18,7
IP 21 21
Insulation class F F
Connection ["] 3/4” -
Air flow  [m3/h] 3000 2700
Acoustic pressure level  [dB(A)]*  48,5 48,5
Sound power level [dB]** 75 75
Max heating water temperature [oC] 90 -
Max operating pressure.[MPa] 1,6 -
Weight of unit [kg] 35,1 25,1

* acoustic pressure level given for optimum installation height, during operation on second step, for the room with average sound absorption, capacity 500 m3, at a distance of 3 m from the unit.
** according to ISO 27327-2.




Dimensions ELiS C-W

elis-c-w-wymiary



Dimensions ELiS C-E

elis-c-e-wymiary

ELiS C-W-100

Tp1 V PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C m3/h kW l/h kPa oC kW l/h kPa oC
Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
0 1050/1250/1400 14,2/15,8/17,0 625/698/749 15,4/18,8/21,3 40,0/37,5/36,0 12,2/13,6/14,6 537/599/643 12,0/14,7/16,7 34,5/32,5/31,0
5 13,3/14,8/15,9 587/655/703 13,7/16,7/19,0 42,5/40,0/38,5 11,3/12,7/13,6 498/556/596 10,5/12,8/14,5 37,0/35,0/33,5
10 12,4/13,8/14,9 547/611/655 12,1/14,7/16,7 45,0/42,5/41,0 10,4/11,6/12,5 458/512/549 9,1/11,0/12,5 39,5/37,5/36,5
15 11,5/12,8/13,8 507/566/608 10,5/12,9/14,6 47,0/45,0/44,0 9,5/10,6/11,4 418/467/501 7,7/9,4/10,6 41,5/40,0/39,0
20 10,6/11,8/12,7 467/522/560 9,1/11,1/12,6 49,5/47,5/46,5 8,6/9,6/10,3 378/422/453 6,4/7,8/8,9 44,0/42,5/41,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C
0 1050/1250/1400 10,3/11,5/12,3 449/501/538 9,0/11,0/12,5 29,0/27,0/26,0 8,3/9,3/9,9 361/403/432 6,4/7,8/8,8 23,5/22,0/21,0
5 9,4/10,5/11,2 410/457/491 7,7/9,3/10,6 31,5/29,5/28,5 7,4/8,2/8,8 322/359/385 5,2/6,3/7,1 26,0/24,5/23,5
10 8,5/9,4/10,1 370/413/443 6,4/7,8/8,8 33,5/32,0/31,5 6,5/7,2/7,7 282/314/337 4,1/5,0/5,6 28,0/27,0/26,5
15 7,5/8,4/9,0 330/368/395 5,2/6,3/7,2 36,0/35,0/34,0 5,5/6,2/6,6 241/269/288 3,1/3,8/4,3 30,5/29,5/29,0
20 6,6/7,4/7,9 289/323/346 4,1/5,0/5,7 38,5/37,5/36,5 4,6/5,1/5,5 199/222/238 2,2/2,7/3,1 32,5/32,0/31,5

ELiS C-W-150

Tp1 V PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C m3/h kW l/h kPa oC kW l/h kPa oC
Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
0 1600/1850/2100 21,9/24,1/26,1 968/1062/1150 16,6/19,6/22,7 40,5/38,5/36,5 18,9/20,8/22,5 832/912/988 13,0/15,3/17,7 35,0/33,0/31,5
5 20,6/22,6/24,4 908/996/1078 14,8/17,5/20,2 43,0/41,0/39,5 17,6/19,3/20,8 772/846/916 11,3/13,4/15,4 37,5/35,5/34,5
10 19,2/21,1/22,8 847/930/1006 13,0/15,4/17,8 45,5/43,5/42,0 16,2/17,7/19,2 710/779/843 9,8/11,5/13,3 40,0/38,0/37,0
15 17,8/19,5/21,1 786/862/933 11,4/13,4/15,5 47,5/46,0/44,5 14,8/16,2/17,5 649/712/770 8,3/9,8/11,3 42,0/40,5/39,5
20 16,4/18,0/19,5 724/794/860 9,8/11,6/13,4 50,0/48,5/47,0 13,4/14,6/15,8 587/643/696 6,9/8,2/9,4 44,5/43,0/42,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C
0 1600/1850/2100 15,9/17,5/18,9 696/764/826 9,7/11,5/13,2 29,5/28,0/26,5 12,9/14,1/15,3 561/615/666 6,9/8,1/9,3 24,0/22,5/21,5
5 14,5/15,9/17,2 636/697/754 8,3/9,8/11,2 32,0/30,5/29,0 11,5/12,6/13,6 500/548/593 5,6/6,6/7,6 26,0/25,0/24,0
10 13,1/14,4/15,6 574/630/681 6,9/8,1/9,4 34,0/33,0/32,0 10,0/11,0/11,9 438/480/519 4,4/5,2/6,0 28,5/27,5/26,5
15 11,7/12,8/13,9 512/562/608 5,6/6,6/7,6 36,5/35,5/34,5 8,6/9,4/10,2 375/411/445 3,4/4,0/4,5 31,0/30,0/29,5
20 10,3/11,3/12,2 449/493/533 4,5/5,2/6,0 39,0/38,0/37,0 7,1/7,8/8,5 311/341/368 2,4/2,8/3,3 33,0/32,5/32,0

ELiS C-W-200

Tp1 V PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C m3/h kW l/h kPa oC kW l/h kPa oC
Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
0 2300/2600/3000 31,4/34,0/37,1 1386/1498/1638 39,4/45,4/53,5 40,5/38,5/36,5 27,2/29,4/32,1 1194/1290/1411 30,9/35,6/41,9 35,0/33,5/31,5
5 29,5/31,9/34,8 1301/1406/1538 35,1/40,5/47,6 43,0/41,0/39,5 25,2/27,3/29,8 1108/1198/1310 27,0/31,1/36,6 37,5/36,0/34,5
10 27,5/29,8/32,5 1215/1313/1436 31,0/35,7/42,0 45,0/43,5/42,0 23,3/25,1/27,5 1022/1105/1207 23,3/26,9/31,6 40,0/38,5/37,0
15 25,6/27,6/30,2 1128/1219/1333 27,1/31,2/36,7 47,5/46,0/44,5 21,3/23,0/25,1 935/1010/1104 19,9/22,9/26,8 42,0/41,0/39,5
20 23,6/25,5/27,9 1040/1125/1229 23,4/26,9/31,7 50,0/48,5/47,0 19,3/20,8/22,8 847/915/1000 16,6/19,1/22,4 44,5/43,5/42,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C
0 2300/2600/3000 22,9/24,8/27,1 1003/1084/1185 23,3/26,8/31,5 29,5/28,0/26,5 18,7/20,2/22,0 813/879/961 16,6/19,1/22,4 24,0/23,0/22,0
5 21,0/22,7/24,8 917/991/1084 19,8/22,8/26,8 32,0/30,5/29,5 16,7/18,0/19,7 727/786/859 13,6/15,6/18,3 26,5/25,5/24,5
10 19,0/20,5/22,4 830/897/981 16,6/19,1/22,4 34,5/33,0/32,0 14,7/15,9/17,3 639/691/755 10,8/12,4/14,5 29,0/28,0/27,0
15 17,0/18,3/20,0 743/802/877 13,6/15,6/18,2 36,5/35,5/34,5 12,6/13,6/14,9 550/595/650 8,3/9,5/11,1 31,0/30,5/29,5
20 14,9/16,1/17,6 654/706/772 10,8/12,4/14,6 39,0/38,0/37,0 10,6/11,4/12,5 460/497/543 6,0/6,9/8,1 33,5/33,0/32,0

To obtain operating parameters concerning other water temperatures, please contact Sales Office.

PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in the heat exchanger

C-E-100 C-E-150 C-E-200
1 bieg 2 bieg 3 bieg 1 bieg 2 bieg 3 bieg 1 bieg 2 bieg 3 bieg
Power Supply [V/Hz] 3x400/50
Unit's rated current(1) [A] 8,8 9,1 9,4 13,7 14,0 14,5 18,1 18,5 18,7
Heating capacity(1) [kW] 6,1 6,4 6,5 9,5 9,7 10,0 12,5 12,8 13,0
Curtain's air temperature rise (ΔT)(1) [°C] 18 16 15 18 16 15 18 16 15
C-E-100 C-E-150 C-E-200
1 bieg 2 bieg 3 bieg 1 bieg 2 bieg 3 bieg 1 bieg 2 bieg 3 bieg
Power Supply [V/Hz] 1x230 V / 50 Hz
Unit's rated current(1)(2) [A] 7,8/17,3/8,8 8,7/18,2/27,3 9,5/19,1/28,2 12,6/26,9/41,1 13,4/27,7/42,1 14,3/28,6/43,5 17,3/35,5/54,2 17,8/36,4/55,5 18,6/37,3/56,2
Heating capacity(1)(2) [kW] 1,8/4,0/6,1 2,0/4,2/6,4 2,2/4,4/6,5 2,9/6,2/9,5 3,1/6,4/9,7 3,3/6,6/10 4,0/8,2/12,5 4,1/8,4/12,8 4,3/8,6/13,0
Curtain's air temperature rise (ΔT)(3) [°C] 8.13.18 7.12.16 6.11.15 8.13.18 7.12.16 6.11.15 8.13.18 7.12.16 6.11.15

(1) At inlet air temperature 10°C
(2) Unit power parameters depending on power connection. The producer does not reccomend using units where power consumption is more than 32 A
(3) Average outlet air temperature for ambient temperature 10°C


uma