LEO AGRO SP

Flowair



Dimensions: Width: 69cm; Height: 66cm; Depth: 58.5cm
Weight: 27.3 Kg

SHORT CHARACTERISTIC:

Fan heater designed to operate indoors.

Casing of the unit is made of plastic. Fan motor with IP66 insulation class and thicker fins on heat exchanger with increased spacing allow to clean the unit with water under pressure. Additionally, clamps which connect the confusor to the heat exchanger enable easy access to the inside of the unit. Such a construction makes the maintenance operations faster and helps in maintaining the unit clean and in optimal condition.
 

PURPOSE:

LEO AGRO SP is designed for operation in agricultural buildings, chicken farms, dryers etc.

CONTROL SYSTEM:

All of the FLOWAIR products have a complete control system. LEO AGRO SP units are available with simple ON/OFF control system, which has low investment cost.

TECHNOLOGY/INNOVATION/BENEFITS:

Construction – heat exchanger with anti-corrosive coating. Fan motor with IP66 insulation class.

Specifications of LEO AGRO SP
Sku
LA-SP

Technical data LEO AGRO SP

LEO AGRO SP
Max. air flow [m3/h] 4600
Max. air flow range [m]* 28
Power supply [V/Hz] 230 / 50
Max. current consumption [A] 2,8
Max. power consumption [W] 550
IP / Insulation class 66 / F
Max. acoustic pressure level [dB(A)]** 62
Max. heating water temperature [oC] 95
Max. operating pressure [MPa] 1,6
Hydraulic connection ["] ¾”
Max. operating temperature [oC] 60
Weight [kg] 27,3
Weight of unit filled with water [kg] 31,0

* Range of horizontal, isothermal air stream at 0,5 m/s speed limit.
** Acoustic pressure level at a distance of 5 m from the unit, in the room of medium capabillity of sound absorption and 1500 m3 of cubic measure.

Main dimensions:

sp

Heating capacities LEO AGRO SP

LEO AGRO SP
V = 4600m3/h
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
0 56,2 2480 20,0 34,0 48,6 2140 16,0 29,5 41 1800 12,0 25,0 33,4 1450 9,0 20,0 31,2 2710 26,0 19,0
5 52,0 2290 17,0 37,0 44,5 1950 13,0 32,5 36,9 1620 11,0 28,0 29,4 1280 7,0 23,0 27,2 2370 20,0 22,0
10 47,8 2110 15,0 40,0 40,4 1780 11,0 35,5 33 1440 9,0 30,5 25,5 1110 7,0 26,0 23,4 2030 15,0 24,5
15 43,8 1930 13,0 43,0 36,4 1600 10,0 38,0 29,1 1270 7,0 33,5 21,6 940 5,0 29,0 19,6 1710 12,0 27,5
20 39,8 1750 11,0 46,0 32,6 1430 8,0 41,0 25,3 1110 6,0 36,5 17,9 780 4,0 31,5 15,9 1380 8,0 30,5

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water flow rate in heat exchanger
Δpw – water pressure drop in heat exchanger

Installation brackets for LEO AGRO SP - easy and quick installation of the unit, as well as optimum air flow around it.


sp

ON/OFF regulation or stepless regulation via microclimate controller.
 
sp
 

Basic functions:

  • 5-step fan speed regulation,
  • fan operation in:
    - continuous mode - after reaching set temperature, heating medium is cutted off while fan is operating at selected step,
    -  intermittent mode - after reaching set temperature, heating medium is cutted off and fan is turned off,
  • room thermostat.

Products list - Control systems for LEO AGRO SP

Our cookie policy

We use cookies to give you the best possible experience on our website. Learn More