LEO KM mixing chamber is designed to work with fan heaters LEO FB 25/45/65/95. It enables delivery of fresh (outside) air into the room. Depending on the requirements, the air flow can be heated via the heat exchanger and then directed inside the building.
The chamber is equipped with three air intakes: 2 of recirculation air and one of fresh air. It is possible to smoothly adjust the degree of dampers opening from 0 to 100%. Thanks to this it is possible to recover heat by recirculation.
LEO KM is available in three versions: KM S, KM L i KM 95
LEO KM with fan heater, UVO roof fans and KM REGULATION system create complete mechanical ventilation system. More information about complete heating and ventilation solutions for buildings can be found in FLOWAIR System menu.
.
LEO KM with fan heaters can be applied in medium and big cubature buildings like industrial halls, warehouses, commercial halls, etc.
KM REGULATION – complete control and protection set for LEO KM + LEO FB..
Construction – modular construction (3 parts) makes possible to install the unit in various configurations. This solution gives various installation options.
Casing of the heater is made of light and durable material – expanded polypropylene (EPP).
Unit is in standard equipped with EU3 class filter (EU4 class filter is an option) installed on air inlet. Its position determines filtration of fresh air or fresh and recirculation air.
LEO FB 10V +LEO KM S | LEO FB 20V + LEO KM S | LEO FB 30V + LEO KM S | LEO FB 25V + LEO KM L | LEO FB 45V + LEO KM L | LEO FB 65V + LEO KM L | LEO FB 95V + LEO KM 95 | |||||||||
Fan | LEO FB V + LEO KM – Axial, single-phase, AC, 3 speed fan | ||||||||||||||
Filter class | EU3 | ||||||||||||||
Max. air flow [m3/h] | 1750 | 1600 | 1500 | 3200 | 3000 | 2800 | 6500 | ||||||||
Power supply [V/Hz] | 230/50 | ||||||||||||||
Max. current consumption [A] | 0.5 | 0.5 | 0.5 | 1.4 | 1.4 | 1.4 | 2.8 | ||||||||
Max. power consumption [W] | 110 | 110 | 110 | 320 | 320 | 320 | 640 | ||||||||
IP / Insulation class | 54/F | ||||||||||||||
Max. acoustic pressure level [dB(A)]** | 47 | 47 | 47 | 54 | 54 | 54 | 57 | ||||||||
Max. air flow range [m]* | 12.0 | 11.0 | 10.0 | 18.0 | 16.5 | 15.5 | 25.0 | ||||||||
Heat exchanger | Cu - Al., S ingle row |
Cu – Al., two row |
Cu – Al., two row |
Cu - Al., S ingle row |
Cu – Al., two row |
Cu – Al., three row |
Cu – Al., two row |
||||||||
Nominal heating power *** [kW ] | 9.2 | 18.7 | 23.3 | 24.2 | 37.3 | 52.0 | 87.0 | ||||||||
Air temperature increase (ΔT )*** [oC] | 15.5 | 34.5 | 46.0 | 22.5 | 37.0 | 55.5 | 39.5 | ||||||||
Max. heating water temperature [oC] | 120 | ||||||||||||||
Max. operating pressure [MPa] | 1.6 | ||||||||||||||
Connection [”] | 1/2 | 3/4 | |||||||||||||
Type of casing | steel + aluminum | ||||||||||||||
Color | Grey***** | ||||||||||||||
Usage | Inside buildings | ||||||||||||||
Maximum operational temperature [oC] | 50 | 60 | |||||||||||||
Position of operation | Can be installed in any desired position | ||||||||||||||
Weight of unit [kg] | 25.9 | 26.8 | 27.9 | 34.3 | 35.5 | 37.8 | 70.2 | ||||||||
Weight of unit filled with water [kg] | 26.6 | 28 | 29.3 | 35.3 | 37.5 | 40.5 | 73.7 |
* Performance without air intake. With air intake, the performance drop by approximately 10%
** Acoustic pressure level at a distance of 5 m from the unit, in the room of medium capabillity of sound absorption and 1500 m3 of cubic measure.
***Range of horizontal isothermal air stream, at 0,5 m/s velocity limit
**** At Maximum air stream flow, temperature of heating medium 90/70°C, temperature at the inlet to the device 0°C
*****Available in any RAL color on request
LEO FB 10 + KM S | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 800 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | 7,1 | 127 | 0,3 | 6,5 | 7,5 | 330 | 1,6 | 8,0 | ||||
-15 | 6,8 | 120 | 0,2 | 10,0 | 7,1 | 313 | 1,5 | 11,5 | 6,2 | 273 | 1,2 | 8,0 |
-10 | 6,4 | 113 | 0,2 | 13,5 | 6,7 | 297 | 1,3 | 15,0 | 5,8 | 256 | 1,1 | 11,5 |
-5 | 6,0 | 107 | 0,2 | 17,5 | 6,3 | 280 | 1,2 | 18,5 | 5,4 | 239 | 0,9 | 15,0 |
0 | 5,6 | 100 | 0,2 | 21,0 | 6,0 | 263 | 1,1 | 22,0 | 5,0 | 221 | 0,8 | 18,5 |
5 | 5,2 | 93 | 0,2 | 24,0 | 5,6 | 245 | 1,0 | 25,5 | 4,6 | 204 | 0,7 | 22,0 |
10 | 4,8 | 86 | 0,1 | 27,5 | 5,2 | 228 | 0,8 | 29,0 | 4,2 | 186 | 0,6 | 25,5 |
15 | 4,4 | 78 | 0,1 | 31,0 | 4,8 | 211 | 0,7 | 32,5 | 3,8 | 169 | 0,5 | 29,0 |
20 | 4,0 | 70 | 0,1 | 34,5 | 4,4 | 193 | 0,6 | 36,0 | 3,4 | 151 | 0,4 | 32,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | ||||||||||||
-10 | 4,9 | 214 | 0,8 | 8,0 | 4,0 | 351 | 2,0 | 5,0 | ||||
-5 | 4,5 | 197 | 0,7 | 11,5 | 3,5 | 153 | 0,5 | 8,0 | 3,6 | 317 | 1,7 | 8,5 |
0 | 4,1 | 179 | 0,6 | 15,0 | 3,1 | 134 | 0,4 | 11,5 | 3,2 | 282 | 1,4 | 12,0 |
5 | 3,7 | 161 | 0,5 | 18,5 | 2,6 | 113 | 0,3 | 14,5 | 2,8 | 246 | 1,1 | 15,5 |
10 | 3,3 | 143 | 0,4 | 22,0 | 2,0 | 86 | 0,2 | 17,5 | 2,4 | 210 | 0,8 | 19,0 |
15 | 2,8 | 124 | 0,3 | 25,5 | 1,7 | 72 | 0,1 | 21,0 | 2,0 | 172 | 0,6 | 22,0 |
20 | 2,4 | 103 | 0,2 | 28,5 | 1,4 | 60 | 0,1 | 25,0 | 1,5 | 132 | 0,4 | 25,5 |
V = 1200 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | 8,5 | 150 | 0,4 | 6,0 | 8,9 | 394 | 2,2 | 7,0 | ||||
-10 | 8,0 | 142 | 0,3 | 10,0 | 8,5 | 373 | 2,0 | 11,0 | 7,3 | 322 | 1,6 | 8,0 |
-5 | 7,5 | 134 | 0,3 | 13,5 | 8,0 | 352 | 1,8 | 14,5 | 6,8 | 300 | 1,4 | 12,0 |
0 | 7,1 | 125 | 0,3 | 17,5 | 7,5 | 330 | 1,6 | 18,5 | 6,3 | 279 | 1,2 | 15,5 |
5 | 6,6 | 117 | 0,2 | 21,0 | 7,0 | 309 | 1,4 | 22,0 | 5,8 | 257 | 1,1 | 19,5 |
10 | 6,1 | 108 | 0,2 | 25,0 | 6,6 | 287 | 1,2 | 26,0 | 5,3 | 235 | 0,9 | 23,0 |
15 | 5,6 | 99 | 0,2 | 28,5 | 6,0 | 265 | 1,1 | 29,5 | 4,8 | 213 | 0,8 | 27,0 |
20 | 5,1 | 90 | 0,2 | 32,0 | 5,5 | 243 | 0,9 | 33,5 | 4,3 | 190 | 0,6 | 30,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | ||||||||||||
-10 | 6,2 | 270 | 1,2 | 5,5 | ||||||||
-5 | 5,7 | 248 | 1,0 | 9,0 | 4,5 | 194 | 0,7 | 6,0 | 4,6 | 399 | 2,6 | 6,5 |
0 | 5,2 | 226 | 0,9 | 13,0 | 3,9 | 171 | 0,6 | 9,5 | 4,1 | 355 | 2,1 | 10,0 |
5 | 4,7 | 204 | 0,7 | 16,5 | 3,4 | 147 | 0,4 | 13,5 | 3,6 | 311 | 1,6 | 14,0 |
10 | 4,1 | 181 | 0,6 | 20,0 | 2,8 | 121 | 0,3 | 17,0 | 3,0 | 265 | 1,2 | 17,5 |
15 | 3,6 | 158 | 0,5 | 24,0 | 1,9 | 83 | 0,2 | 19,5 | 2,5 | 219 | 0,9 | 21,0 |
20 | 3,1 | 134 | 0,4 | 27,5 | 1,6 | 69 | 0,1 | 24,0 | 2,0 | 171 | 0,6 | 25,0 |
V = 1750 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | ||||||||||||
-10 | 9,8 | 173 | 0,4 | 6,5 | 10,4 | 458 | 2,9 | 7,5 | 9,0 | 395 | 2,3 | 5,5 |
-5 | 9,2 | 163 | 0,4 | 10,5 | 9,8 | 432 | 2,6 | 11,5 | 8,4 | 369 | 2,0 | 9,0 |
0 | 8,6 | 153 | 0,4 | 14,5 | 9,2 | 405 | 2,3 | 15,5 | 7,8 | 342 | 1,8 | 13,0 |
5 | 8,0 | 143 | 0,3 | 18,5 | 8,5 | 379 | 2,1 | 19,5 | 7,2 | 315 | 1,5 | 17,0 |
10 | 7,4 | 132 | 0,3 | 22,5 | 8,0 | 352 | 1,8 | 23,5 | 6,6 | 288 | 1,3 | 21,0 |
15 | 6,8 | 121 | 0,2 | 26,5 | 7,4 | 325 | 1,6 | 27,5 | 6,0 | 261 | 1,1 | 25,0 |
20 | 6,2 | 111 | 0,2 | 30,5 | 6,8 | 298 | 1,3 | 31,0 | 5,3 | 233 | 0,9 | 29,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | ||||||||||||
-10 | ||||||||||||
-5 | 7,0 | 305 | 1,5 | 7,0 | ||||||||
0 | 6,4 | 278 | 1,3 | 11,0 | 4,9 | 212 | 0,8 | 8,0 | 5,0 | 437 | 3,0 | 8,5 |
5 | 5,7 | 251 | 1,1 | 14,5 | 4,2 | 183 | 0,6 | 12,0 | 4,4 | 382 | 2,4 | 12,5 |
10 | 5,1 | 223 | 0,9 | 18,5 | 3,5 | 153 | 0,5 | 16,0 | 3,8 | 327 | 1,8 | 16,5 |
15 | 4,5 | 195 | 0,7 | 22,5 | 2,8 | 120 | 0,3 | 19,5 | 3,1 | 271 | 1,3 | 20,0 |
20 | 3,8 | 166 | 0,5 | 26,5 | 1,8 | 77 | 0,1 | 23,0 | 2,5 | 213 | 0,8 | 24,0 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 20 + KM S | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 550 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 12,7 | 225 | 1,2 | 43,5 | 12,2 | 537 | 6,3 | 41 | 10,9 | 479 | 5,3 | 34 |
-20 | 12,1 | 215 | 1,1 | 45,5 | 12 | 512 | 5,8 | 42,5 | 10,3 | 453 | 4,8 | 36 |
-15 | 11,5 | 205 | 1,0 | 47,5 | 11 | 486 | 5,3 | 44,5 | 9,7 | 428 | 4,4 | 37,5 |
-10 | 11,0 | 195 | 0,9 | 49,0 | 10,4 | 460 | 4,8 | 46,5 | 9,1 | 402 | 3,9 | 39,5 |
-5 | 10,4 | 185 | 0,8 | 51,0 | 9,8 | 435 | 4,4 | 48 | 8,6 | 376 | 3,5 | 41 |
0 | 9,8 | 175 | 0,7 | 53,0 | 9,3 | 409 | 3,9 | 50 | 8 | 351 | 3,1 | 43 |
5 | 9,3 | 164 | 0,7 | 54,5 | 8,7 | 384 | 3,5 | 51,5 | 7,4 | 325 | 2,7 | 44,5 |
10 | 8,7 | 154 | 0,6 | 56,5 | 8,1 | 358 | 3,1 | 53,5 | 6,8 | 299 | 2,3 | 46,5 |
15 | 8,1 | 144 | 0,5 | 58,0 | 7,5 | 332 | 2,7 | 55 | 6,2 | 273 | 2 | 48 |
20 | 7,5 | 134 | 0,5 | 59,5 | 6,9 | 305 | 2,3 | 57 | 5,6 | 246 | 1,6 | 49,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 9,6 | 421 | 4,4 | 27 | 8,3 | 363 | 3,5 | 20 | 8 | 701 | 11,6 | 18,5 |
-20 | 9 | 395 | 3,9 | 29 | 7,7 | 337 | 3,1 | 22 | 7,5 | 650 | 10,1 | 20,5 |
-15 | 8,4 | 370 | 3,5 | 30,5 | 7,1 | 311 | 2,7 | 23,5 | 6,9 | 600 | 8,7 | 22 |
-10 | 7,9 | 344 | 3,1 | 32,5 | 6,5 | 286 | 2,3 | 25,5 | 6,3 | 549 | 7,4 | 24 |
-5 | 7,3 | 318 | 2,7 | 34 | 6 | 260 | 1,9 | 27 | 5,7 | 497 | 6,3 | 26 |
0 | 6,7 | 292 | 2,3 | 36 | 5,3 | 234 | 1,6 | 29 | 5,1 | 446 | 5,2 | 27,5 |
5 | 6,1 | 267 | 2 | 37,5 | 4,7 | 207 | 1,3 | 30,5 | 4,5 | 394 | 4,2 | 29 |
10 | 5,5 | 240 | 1,6 | 39,5 | 4,1 | 180 | 1 | 32 | 3,9 | 342 | 3,2 | 31 |
15 | 4,9 | 214 | 1,3 | 41 | 3,5 | 152 | 0,7 | 33,5 | 3,3 | 289 | 2,4 | 32,5 |
20 | 4,2 | 186 | 1 | 42,5 | 2,8 | 123 | 0,5 | 35 | 2,7 | 235 | 1,7 | 34,5 |
V = 1000 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 18,7 | 333 | 2,3 | 31,0 | 18,2 | 806 | 13,1 | 29,5 | 16,3 | 718 | 11 | 23,5 |
-20 | 17,9 | 318 | 2,2 | 33,5 | 17,4 | 768 | 12 | 31,5 | 15,5 | 680 | 10 | 26 |
-15 | 17,1 | 303 | 2,0 | 36,0 | 16,5 | 730 | 11 | 34 | 14,6 | 642 | 9 | 28,5 |
-10 | 16,2 | 289 | 1,8 | 38,0 | 15,6 | 692 | 9,9 | 36,5 | 13,7 | 604 | 8 | 31 |
-5 | 15,4 | 274 | 1,6 | 40,5 | 14,8 | 653 | 9 | 39 | 12,8 | 565 | 7,2 | 33 |
0 | 14,5 | 259 | 1,5 | 43,0 | 13,9 | 615 | 8,1 | 41 | 12 | 527 | 6,3 | 35,5 |
5 | 13,7 | 244 | 1,3 | 45,5 | 13 | 576 | 7,2 | 43,5 | 11,1 | 488 | 5,5 | 38 |
10 | 12,8 | 228 | 1,2 | 48,0 | 12,1 | 537 | 6,3 | 46 | 10,2 | 449 | 4,7 | 40 |
15 | 12,0 | 213 | 1,1 | 50,0 | 11.3 | 498 | 5,5 | 48 | 9,3 | 409 | 4 | 42,5 |
20 | 11,1 | 198 | 0,9 | 52,5 | 10,4 | 458 | 4,8 | 50 | 8,4 | 369 | 3,3 | 44,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 14,4 | 631 | 9 | 18 | 12,5 | 544 | 7,2 | 12,2 | 12,1 | 1054 | 24 | 11 |
-20 | 13,5 | 593 | 8,1 | 20 | 11,6 | 506 | 6,3 | 14,5 | 11,2 | 978 | 21 | 13,5 |
-15 | 12,6 | 555 | 7,2 | 22,7 | 10,7 | 467 | 5,5 | 17 | 10,3 | 902 | 18,1 | 15,5 |
-10 | 11,8 | 516 | 6,3 | 25 | 9,8 | 429 | 4,7 | 19 | 9,5 | 825 | 15,5 | 18 |
-5 | 10,9 | 478 | 5,5 | 27,5 | 8,9 | 390 | 4 | 21,5 | 8,6 | 748 | 13 | 20,5 |
0 | 10 | 439 | 4,7 | 29,5 | 8 | 351 | 3,3 | 23,8 | 7,7 | 671 | 10,7 | 23 |
5 | 9,1 | 400 | 4 | 32 | 7,1 | 312 | 2,7 | 26 | 6,8 | 593 | 8,6 | 25 |
10 | 8,2 | 361 | 3,3 | 34 | 6,2 | 272 | 2,1 | 28,5 | 5,9 | 514 | 6,6 | 27,5 |
15 | 7,3 | 321 | 2,7 | 36,5 | 5,3 | 231 | 1,6 | 30,5 | 5 | 434 | 4,9 | 29,5 |
20 | 6,4 | 280 | 2,1 | 38,5 | 4,3 | 188 | 1,1 | 32,5 | 4 | 354 | 3,4 | 32 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 25 + KM L | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 1600 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 22,1 | 392 | 1,5 | 16,0 | 20,1 | 885 | 6,7 | 12,5 | 17,8 | 784 | 5,7 | 8,0 |
-20 | 21,0 | 374 | 1,4 | 19,0 | 19,1 | 843 | 6,3 | 15,5 | 16,9 | 741 | 5,1 | 11,5 |
-15 | 20,0 | 356 | 1,3 | 22,0 | 18,1 | 800 | 5,7 | 18,5 | 15,9 | 699 | 4,6 | 14,5 |
-10 | 19,0 | 338 | 1,2 | 25,5 | 17,2 | 757 | 5,2 | 22,0 | 14,9 | 656 | 4,1 | 17,0 |
-5 | 18,0 | 319 | 1,0 | 28,5 | 16,2 | 714 | 4,6 | 25,0 | 13,9 | 612 | 3,6 | 21,0 |
0 | 16,9 | 301 | 0,9 | 31,5 | 15,2 | 671 | 4,2 | 28,0 | 12,9 | 569 | 3,2 | 24,0 |
5 | 15,9 | 282 | 0,8 | 34,5 | 14,2 | 627 | 3,7 | 31,0 | 12,0 | 525 | 2,8 | 27,0 |
10 | 14,8 | 263 | 0,7 | 37,0 | 13,2 | 583 | 3,2 | 34,5 | 10,9 | 480 | 2,4 | 30,0 |
15 | 13,7 | 244 | 0,7 | 40,0 | 12,2 | 538 | 2,8 | 37,5 | 9,9 | 435 | 2,0 | 33,5 |
20 | 12,6 | 224 | 0,6 | 43,0 | 11,2 | 493 | 2,4 | 40,5 | 8,9 | 390 | 1,6 | 36,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | 14,6 | 640 | 4,1 | 7,0 | ||||||||
-15 | 13,6 | 597 | 3,6 | 10,5 | 11,3 | 494 | 2,7 | 6,0 | 12,0 | 1040 | 10,3 | 7,0 |
-10 | 12,7 | 554 | 3,1 | 13,5 | 10,3 | 451 | 2,3 | 9,0 | 10,9 | 948 | 8,7 | 10,5 |
-5 | 11,7 | 510 | 2,7 | 16,5 | 9,3 | 407 | 1,9 | 12,5 | 9,8 | 856 | 7,2 | 13,5 |
0 | 10,7 | 466 | 2,3 | 19,5 | 8,3 | 362 | 1,5 | 15,5 | 8,8 | 765 | 5,9 | 16,5 |
5 | 9,6 | 422 | 1,9 | 23,0 | 7,3 | 316 | 1,2 | 18,5 | 7,7 | 671 | 4,7 | 19,0 |
10 | 8,6 | 377 | 1,6 | 26,0 | 6,2 | 270 | 0,9 | 21,5 | 6,6 | 577 | 3,6 | 22,0 |
15 | 7,6 | 331 | 1,3 | 29,0 | 5,1 | 221 | 0,6 | 24,5 | 5,5 | 481 | 2,6 | 25,0 |
20 | 6,5 | 285 | 1,0 | 32,0 | 3,8 | 166 | 0,4 | 27,0 | 4,4 | 385 | 1,7 | 28,0 |
V = 2500 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 28,1 | 499 | 2,3 | 10,0 | 25,4 | 1120 | 10,5 | 6,6 | (2) | |||
-20 | 26,8 | 476 | 2,1 | 13,5 | 24,2 | 1066 | 9,6 | 10,0 | 21,3 | 938 | 7,8 | 6,5 |
-15 | 25,5 | 453 | 2,0 | 16,5 | 22,9 | 1012 | 8,8 | 13,5 | 20,1 | 883 | 7,0 | 10,0 |
-10 | 24,2 | 430 | 1,8 | 20,0 | 21,5 | 957 | 7,9 | 17,0 | 18,9 | 829 | 6,3 | 13,5 |
-5 | 22,9 | 406 | 1,6 | 23,5 | 20,5 | 903 | 7,1 | 20,5 | 17,6 | 774 | 5,5 | 17,0 |
0 | 21,5 | 383 | 1,5 | 26,5 | 19,2 | 848 | 6,3 | 23,5 | 16,4 | 719 | 4,8 | 20,0 |
5 | 20,2 | 359 | 1,3 | 30,0 | 18,0 | 793 | 5,6 | 27,0 | 16,1 | 706 | 4,7 | 25,0 |
10 | 18,8 | 335 | 1,1 | 33,0 | 16,7 | 737 | 4,9 | 30,5 | 14,7 | 646 | 4 | 28,0 |
15 | 17,5 | 310 | 1,0 | 36,5 | 15,4 | 680 | 4,3 | 34,0 | 13,3 | 586 | 3,4 | 31,5 |
20 | 16,1 | 286 | 0,9 | 39,5 | 14,1 | 623 | 3,6 | 37,0 | 11,9 | 525 | 2,8 | 34,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | 18,4 | 803 | 6,1 | 8,0 | ||||||||
-10 | 17,0 | 745 | 5,3 | 11,0 | 13,9 | 607 | 3,8 | 7,0 | 14,3 | 1243 | 14,2 | 7,0 |
-5 | 15,7 | 686 | 4,6 | 14,5 | 12,6 | 548 | 3,2 | 10,5 | 12,9 | 1123 | 11,8 | 10,5 |
0 | 14,3 | 627 | 3,9 | 17,5 | 11,2 | 488 | 2,6 | 14,0 | 11,5 | 1001 | 9,6 | 13,5 |
5 | 13,0 | 568 | 3,3 | 21,0 | 9,8 | 427 | 2,1 | 17,0 | 10,1 | 879 | 7,6 | 17,0 |
10 | 11,6 | 507 | 2,7 | 24,0 | 8,4 | 365 | 1,6 | 20,5 | 8,7 | 756 | 5,8 | 20,0 |
15 | 10,2 | 446 | 2,1 | 27,5 | 6,9 | 302 | 1,1 | 23,5 | 7,3 | 631 | 4,2 | 23,5 |
20 | 8,8 | 384 | 1,6 | 30,5 | 5,4 | 235 | 0,7 | 26,5 | 5,8 | 505 | 2,8 | 26,5 |
V = 3200 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 33,1 | 589 | 3,1 | 6,0 | (2) | (2) | ||||||
-20 | 31,6 | 562 | 2,9 | 8,0 | 30,4 | 1343 | 14,7 | 8,5 | ||||
-15 | 30,1 | 534 | 2,6 | 13,0 | 28,9 | 1274 | 13,3 | 12,0 | 25,3 | 1112 | 10,7 | 8,5 |
-10 | 28,5 | 507 | 2,4 | 16,5 | 27,3 | 1206 | 12,0 | 15,5 | 23,7 | 1043 | 9,5 | 12,0 |
-5 | 27,0 | 479 | 2,2 | 20,0 | 25,8 | 1137 | 10,8 | 19,0 | 22,2 | 974 | 8,4 | 15,5 |
0 | 25,4 | 451 | 1,9 | 23,5 | 24,2 | 1068 | 9,7 | 22,5 | 20,6 | 905 | 7,4 | 19,0 |
5 | 23,8 | 423 | 1,7 | 27,0 | 22,6 | 998 | 8,5 | 26,0 | 19,0 | 835 | 6,4 | 22,5 |
10 | 22,2 | 395 | 1,5 | 30,5 | 21,0 | 927 | 7,5 | 29,5 | 17,4 | 764 | 5,4 | 26,0 |
15 | 20,6 | 366 | 1,3 | 34,0 | 19,4 | 856 | 6,5 | 33,0 | 15,8 | 692 | 4,5 | 29,5 |
20 | 18,9 | 336 | 1,2 | 37,5 | 17,8 | 784 | 5,5 | 36,5 | 14,1 | 620 | 3,7 | 33,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | (2) | (2) | (2) | |||||||||
-20 | ||||||||||||
-15 | ||||||||||||
-10 | 20,1 | 881 | 7,2 | 8,5 | 16,5 | 718 | 5,2 | 5,5 | 16,5 | 1437 | 18,5 | 5,5 |
-5 | 18,5 | 811 | 6,2 | 12,0 | 14,9 | 648 | 4,3 | 9,0 | 14,9 | 1297 | 15,4 | 8,5 |
0 | 17,0 | 742 | 5,3 | 15,5 | 13,2 | 577 | 3,5 | 12,5 | 13,3 | 1157 | 12,5 | 12,5 |
5 | 15,3 | 671 | 4,4 | 19,0 | 11,6 | 506 | 2,8 | 15,5 | 11,7 | 1015 | 9,9 | 15,5 |
10 | 13,7 | 600 | 3,6 | 22,5 | 9,9 | 433 | 2,1 | 19,0 | 10,3 | 872 | 7,5 | 19,0 |
15 | 12,1 | 527 | 2,9 | 26,0 | 8,2 | 358 | 1,5 | 22,5 | 8,4 | 728 | 5,4 | 22,5 |
20 | 10,4 | 454 | 2,2 | 29,5 | 6,4 | 281 | 1,0 | 26,0 | 6,7 | 583 | 3,6 | 26,0 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 30 + KM S | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 300 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 9,5 | 169 | 0,4 | 69,5 | 9,0 | 399 | 2,0 | 65,0 | 8,1 | 356 | 1,6 | 55,5 |
-20 | 9,1 | 161 | 0,3 | 70,0 | 8,6 | 380 | 1,8 | 65,5 | 7,7 | 337 | 1,5 | 56,0 |
-15 | 8,6 | 153 | 0,3 | 70,5 | 8,2 | 361 | 1,6 | 66,0 | 7,2 | 317 | 1,4 | 56,5 |
-10 | 8,2 | 145 | 0,3 | 71,0 | 7,7 | 341 | 1,5 | 66,5 | 6,8 | 298 | 1,2 | 57,0 |
-5 | 7,7 | 137 | 0,3 | 71,5 | 7,3 | 322 | 1,3 | 67,0 | 6,3 | 278 | 1,1 | 57,5 |
0 | 7,3 | 129 | 0,2 | 71,5 | 6,9 | 303 | 1,2 | 67,5 | 5,9 | 259 | 0,9 | 58,0 |
5 | 6,8 | 121 | 0,2 | 72,0 | 6,4 | 283 | 1,1 | 68,0 | 5,5 | 240 | 0,8 | 58,5 |
10 | 6,4 | 113 | 0,2 | 72,5 | 6,0 | 264 | 0,9 | 68,5 | 5,0 | 220 | 0,7 | 59,0 |
15 | 5,9 | 105 | 0,2 | 72,5 | 5,5 | 245 | 0,8 | 69,0 | 4,6 | 201 | 0,6 | 59,5 |
20 | 5,4 | 97 | 0,1 | 72,5 | 5,1 | 226 | 0,7 | 69,5 | 4,1 | 181 | 0,5 | 60,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 7,1 | 312 | 1,4 | 46,0 | 6,2 | 268 | 1,1 | 36,0 | 6,0 | 522 | 3,6 | 34,5 |
-20 | 6,7 | 293 | 1,2 | 46,5 | 5,7 | 249 | 1,0 | 36,5 | 5,6 | 483 | 3,1 | 35,0 |
-15 | 6,2 | 273 | 1,1 | 47,0 | 5,3 | 229 | 0,8 | 37,0 | 5,1 | 445 | 2,7 | 35,5 |
-10 | 5,8 | 254 | 1,0 | 47,5 | 4,8 | 209 | 0,7 | 37,5 | 4,7 | 406 | 2,3 | 36,3 |
-5 | 5,4 | 234 | 0,8 | 48,0 | 4,3 | 189 | 0,6 | 38,0 | 4,2 | 368 | 1,9 | 37,0 |
0 | 4,9 | 215 | 0,7 | 48,5 | 3,9 | 168 | 0,5 | 38,0 | 3,8 | 329 | 1,6 | 37,5 |
5 | 4,5 | 195 | 0,6 | 49,0 | 3,4 | 147 | 0,4 | 38,0 | 3,3 | 290 | 1,3 | 38,0 |
10 | 4,0 | 175 | 0,5 | 49,0 | 2,8 | 123 | 0,3 | 38,0 | 2,9 | 250 | 1,0 | 38,0 |
15 | 3,5 | 155 | 0,4 | 49,5 | 2,4 | 102 | 0,2 | 38,0 | 2,4 | 210 | 0,7 | 38,5 |
20 | 3,1 | 133 | 0,3 | 49,5 | 2,0 | 86 | 0,2 | 39,0 | 1,9 | 168 | 0,5 | 39,0 |
V = 800 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 20,2 | 359 | 1,4 | 50,0 | 19,8 | 872 | 8,0 | 48,5 | 17,6 | 775 | 6,6 | 41,0 |
-20 | 19,3 | 343 | 1,3 | 51,5 | 18,8 | 830 | 7,3 | 50,0 | 16,7 | 733 | 6,0 | 42,0 |
-15 | 18,3 | 326 | 1,2 | 53,0 | 17,8 | 787 | 6,6 | 51,0 | 15,7 | 691 | 5,4 | 43,5 |
-10 | 17,4 | 309 | 1,1 | 54,5 | 16,9 | 745 | 6,0 | 52,5 | 14,8 | 648 | 4,8 | 45,0 |
-5 | 16,4 | 292 | 1,0 | 56,0 | 15,9 | 702 | 5,4 | 54,0 | 13,8 | 606 | 4,3 | 46,0 |
0 | 15,5 | 276 | 0,9 | 57,5 | 15,0 | 660 | 4,8 | 55,5 | 12,8 | 564 | 3,9 | 47,5 |
5 | 14,5 | 259 | 0,8 | 58,5 | 14,0 | 618 | 4,3 | 56,5 | 11,9 | 521 | 3,3 | 49,0 |
10 | 13,6 | 242 | 0,7 | 60,0 | 13,0 | 576 | 3,8 | 58,0 | 10,9 | 479 | 2,8 | 50,0 |
15 | 12,7 | 225 | 0,6 | 61,0 | 12,1 | 533 | 3,3 | 59,0 | 9,9 | 436 | 2,4 | 51,5 |
20 | 11,7 | 208 | 0,5 | 62,5 | 11,1 | 491 | 2,8 | 60,5 | 9,0 | 394 | 2,0 | 52,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 15,5 | 679 | 5,4 | 33,0 | 13,4 | 583 | 4,3 | 25,0 | 13,1 | 1140 | 14,6 | 24,0 |
-20 | 14,6 | 637 | 4,8 | 34,0 | 12,4 | 541 | 3,8 | 26,0 | 12,1 | 1056 | 12,7 | 25,0 |
-15 | 13,6 | 595 | 4,3 | 35,5 | 11,4 | 498 | 3,2 | 27,5 | 11,2 | 971 | 10,9 | 26,5 |
-10 | 12,6 | 552 | 3,8 | 37,0 | 10,5 | 456 | 2,8 | 29,0 | 10,2 | 887 | 9,3 | 28,0 |
-5 | 11,6 | 510 | 3,3 | 38,0 | 9,5 | 413 | 2,3 | 30,0 | 9,2 | 802 | 9,2 | 29,0 |
0 | 10,7 | 467 | 2,8 | 39,5 | 8,5 | 370 | 1,9 | 31,4 | 8,2 | 718 | 6,3 | 30,5 |
5 | 9,7 | 424 | 2,3 | 41,0 | 7,5 | 326 | 1,5 | 32,5 | 7,3 | 632 | 5,1 | 32,0 |
10 | 8,7 | 382 | 1,9 | 42,0 | 6,5 | 282 | 1,2 | 34,0 | 6,3 | 547 | 3,9 | 33,0 |
15 | 7,7 | 338 | 1,6 | 43,5 | 5,4 | 236 | 0,9 | 35,0 | 5,3 | 460 | 2,9 | 34,5 |
20 | 6,7 | 295 | 1,2 | 44,5 | 4,3 | 188 | 0,6 | 35,5 | 4,3 | 373 | 2,0 | 35,5 |
V = 1500 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 30,9 | 549 | 3,0 | 36,5 | 30,9 | 1360 | 17,9 | 36,0 | 27,5 | 1208 | 14,8 | 29,5 |
-20 | 29,4 | 523 | 2,8 | 38,5 | 29,3 | 1294 | 16,3 | 38,0 | 26,0 | 1142 | 13,4 | 31,5 |
-15 | 28,0 | 498 | 2,6 | 40,5 | 27,8 | 1228 | 14,9 | 40,0 | 24,5 | 1076 | 12,0 | 33,5 |
-10 | 26,5 | 472 | 2,3 | 42,5 | 26,3 | 1161 | 13,4 | 42,0 | 23,0 | 1010 | 10,7 | 35,5 |
-5 | 25,1 | 446 | 2,1 | 44,5 | 24,8 | 1095 | 12,1 | 44,0 | 21,5 | 944 | 9,5 | 37,5 |
0 | 23,7 | 421 | 1,9 | 46,5 | 23,3 | 1029 | 10,8 | 46,0 | 20,0 | 878 | 8,3 | 39,5 |
5 | 22,2 | 395 | 1,7 | 48,5 | 21,8 | 963 | 9,6 | 48,0 | 18,5 | 811 | 7,2 | 41,5 |
10 | 20,8 | 369 | 1,5 | 50,5 | 20,3 | 896 | 8,4 | 50,0 | 17,0 | 744 | 6,2 | 43,0 |
15 | 19,3 | 343 | 1,3 | 52,5 | 18,8 | 830 | 7,3 | 51,5 | 15,4 | 678 | 5,2 | 45,0 |
20 | 17,8 | 317 | 1,1 | 54,5 | 17,3 | 764 | 6,3 | 53,5 | 13,9 | 611 | 4,3 | 47,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 24,2 | 1057 | 12,0 | 23,0 | 20,8 | 906 | 9,5 | 16,5 | 20,5 | 1780 | 32,6 | 15,5 |
-20 | 22,5 | 991 | 10,7 | 25,0 | 19,3 | 841 | 8,3 | 18,5 | 19,0 | 1648 | 28,4 | 17,5 |
-15 | 21,2 | 925 | 9,5 | 27,0 | 17,8 | 774 | 7,1 | 20,5 | 17,4 | 1517 | 24,4 | 19,5 |
-10 | 19,6 | 859 | 8,3 | 29,0 | 16,3 | 708 | 6,1 | 22,0 | 15,9 | 1384 | 20,7 | 21,5 |
-5 | 18,1 | 793 | 7,2 | 31,0 | 14,7 | 642 | 5,1 | 24,0 | 14,4 | 1252 | 17,2 | 23,5 |
0 | 16,6 | 726 | 6,1 | 33,0 | 13,2 | 575 | 4,2 | 26,0 | 12,9 | 1119 | 14,1 | 25,5 |
5 | 15,1 | 660 | 5,2 | 34,5 | 11,6 | 507 | 3,4 | 28,0 | 11,3 | 986 | 11,2 | 27,5 |
10 | 13,5 | 593 | 4,2 | 36,5 | 10,1 | 439 | 2,6 | 30,0 | 9,8 | 851 | 8,6 | 29,0 |
15 | 12,0 | 525 | 3,4 | 38,5 | 8,5 | 370 | 1,9 | 31,5 | 8,2 | 716 | 6,3 | 31,0 |
20 | 10,5 | 457 | 2,7 | 40,0 | 6,9 | 298 | 1,3 | 33,5 | 6,7 | 580 | 4,3 | 33,0 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 45 + KM L | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 1250 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 29,6 | 526 | 1,3 | 45,5 | 27,6 | 1217 | 6,2 | 40,5 | 24,6 | 1083 | 5,2 | 33,5 |
-20 | 28,2 | 502 | 1,2 | 47,0 | 26,3 | 1159 | 5,7 | 42,5 | 23,3 | 1024 | 4,7 | 35,5 |
-15 | 26,9 | 478 | 1,1 | 49,0 | 24,9 | 1100 | 5,2 | 44,5 | 22,0 | 965 | 4,2 | 37,0 |
-10 | 25,6 | 454 | 1,9 | 50,5 | 23,6 | 1041 | 4,7 | 46,0 | 20,6 | 907 | 3,8 | 39,0 |
-5 | 24,2 | 430 | 0,9 | 52,5 | 22,3 | 982 | 4,2 | 48,0 | 19,3 | 848 | 3,4 | 41,0 |
0 | 22,9 | 406 | 0,8 | 54,0 | 20,9 | 924 | 3,8 | 49,5 | 18,0 | 789 | 3,0 | 42,5 |
5 | 21,5 | 382 | 0,8 | 56,0 | 19,6 | 965 | 3,4 | 51,3 | 16,6 | 730 | 2,6 | 44,0 |
10 | 20,1 | 358 | 0,7 | 57,5 | 18,2 | 805 | 3,0 | 53,0 | 15,2 | 670 | 2,2 | 46,0 |
15 | 18,7 | 333 | 0,6 | 59,0 | 16,9 | 745 | 2,6 | 54,5 | 13,9 | 609 | 1,9 | 47,5 |
20 | 17,3 | 308 | 0,5 | 60,5 | 15,5 | 684 | 2,2 | 56,5 | 12,5 | 548 | 1,6 | 49,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 21,7 | 948 | 4,3 | 26,5 | 18,7 | 814 | 3,4 | 19,5 | 15,6 | 1355 | 8,5 | 21,5 |
-20 | 20,3 | 890 | 3,8 | 28,5 | 17,3 | 755 | 3,0 | 21,5 | 14,4 | 1256 | 7,5 | 23,0 |
-15 | 19,0 | 831 | 3,4 | 30,0 | 16,0 | 696 | 2,6 | 23,0 | 13,3 | 1156 | 6,4 | 24,5 |
-10 | 17,7 | 772 | 3,0 | 32,0 | 14,6 | 637 | 2,2 | 25,0 | 12,1 | 1056 | 5,5 | 26,0 |
-5 | 16,3 | 713 | 2,6 | 33,5 | 13,3 | 577 | 1,8 | 26,5 | 11,0 | 956 | 4,6 | 27,5 |
0 | 14,9 | 654 | 2,2 | 35,5 | 11,9 | 517 | 1,5 | 28,0 | 9,8 | 855 | 3,8 | 29,0 |
5 | 13,6 | 594 | 1,9 | 37,0 | 10,5 | 456 | 1,2 | 29,5 | 8,7 | 754 | 3,0 | 30,5 |
10 | 12,2 | 534 | 1,5 | 38,5 | 9,0 | 394 | 0,9 | 31,5 | 7,5 | 652 | 2,3 | 32,0 |
15 | 10,8 | 473 | 1,2 | 40,5 | 7,5 | 330 | 0,7 | 33,0 | 6,3 | 549 | 1,7 | 33,5 |
20 | 9,4 | 410 | 1,0 | 42,0 | 6,0 | 261 | 0,5 | 34,0 | 5,1 | 444 | 1,2 | 35,0 |
V = 2050 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 41,2 | 732 | 2,4 | 35,0 | 38,6 | 1703 | 11,5 | 31,0 | 34,5 | 1514 | 9,5 | 25,0 |
-20 | 39,3 | 699 | 2,2 | 37,0 | 36,7 | 1621 | 10,5 | 33,5 | 32,6 | 1432 | 8,6 | 27,5 |
-15 | 37,4 | 666 | 2,0 | 39,4 | 34,9 | 1539 | 9,5 | 35,5 | 30,7 | 1350 | 7,8 | 29,5 |
-10 | 35,6 | 632 | 1,8 | 41,5 | 33,0 | 1457 | 8,6 | 38,0 | 28,9 | 1268 | 6,9 | 32,0 |
-5 | 33,7 | 599 | 1,7 | 44,0 | 31,1 | 1374 | 7,8 | 40,0 | 27,0 | 1185 | 6,1 | 34,0 |
0 | 47,7 | 848 | 2,2 | 69,0 | 29,3 | 1292 | 7,0 | 42,5 | 26,1 | 1103 | 5,4 | 36,0 |
5 | 31,8 | 566 | 1,5 | 46,0 | 27,4 | 1209 | 6,2 | 44,5 | 23,2 | 1020 | 4,7 | 38,5 |
10 | 29,9 | 532 | 1,3 | 48,0 | 25,5 | 1126 | 5,4 | 46,5 | 21,3 | 936 | 4,0 | 40,5 |
15 | 26,1 | 465 | 1,1 | 52,5 | 23,6 | 1041 | 4,7 | 49,0 | 19,4 | 851 | 3,4 | 43,0 |
20 | 24,2 | 431 | 0,9 | 54,5 | 21,7 | 956 | 4,0 | 51,0 | 17,4 | 766 | 2,8 | 45,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 30,3 | 1325 | 7,8 | 19,0 | 26,1 | 1137 | 6,1 | 13,0 | 25,6 | 2228 | 20,9 | 12,5 |
-20 | 28,4 | 1244 | 6,9 | 21,5 | 24,2 | 1055 | 5,4 | 15,0 | 23,7 | 2065 | 18,2 | 14,5 |
-15 | 26,6 | 1162 | 6,1 | 23,5 | 22,3 | 973 | 4,6 | 17,5 | 21,8 | 1901 | 15,7 | 16,5 |
-10 | 24,7 | 1079 | 5,4 | 26,0 | 20,4 | 890 | 4,0 | 19,5 | 20,0 | 1736 | 13,3 | 19,0 |
-5 | 22,8 | 997 | 4,7 | 28,0 | 18,5 | 807 | 3,3 | 22,0 | 18,1 | 1571 | 11,1 | 21,0 |
0 | 20,9 | 914 | 4,0 | 30,0 | 16,6 | 723 | 2,7 | 24,0 | 16,2 | 1405 | 9,1 | 23,5 |
5 | 19,0 | 830 | 3,4 | 32,5 | 14,7 | 639 | 2,2 | 26,0 | 14,2 | 1238 | 7,3 | 25,5 |
10 | 17,0 | 746 | 2,8 | 34,5 | 12,7 | 553 | 1,7 | 28,0 | 12,3 | 1071 | 5,6 | 27,5 |
15 | 15,1 | 660 | 2,2 | 36,5 | 10,7 | 465 | 1,3 | 30,5 | 10,4 | 902 | 4,1 | 30,0 |
20 | 13,1 | 574 | 1,7 | 38,5 | 8,6 | 374 | 0,9 | 32,5 | 8,4 | 731 | 2,8 | 32,0 |
V = 3000 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 52,3 | 929 | 3,7 | 27,0 | 49,2 | 2169 | 17,8 | 24,0 | 43,9 | 1928 | 14,8 | 18,5 |
-20 | 49,9 | 887 | 3,4 | 29,5 | 46,8 | 2065 | 16,3 | 26,5 | 41,5 | 1823 | 13,4 | 21,0 |
-15 | 47,5 | 845 | 3,1 | 32,0 | 44,4 | 1960 | 14,8 | 29,0 | 39,1 | 1719 | 12,0 | 24,0 |
-10 | 45,1 | 803 | 2,8 | 34,5 | 42,0 | 1856 | 14,4 | 31,5 | 36,7 | 1614 | 10,7 | 26,5 |
-5 | 42,8 | 760 | 2,6 | 37,5 | 39,7 | 1750 | 12,1 | 34,0 | 34,3 | 1509 | 9,5 | 29,0 |
0 | 40,4 | 718 | 2,3 | 40,0 | 37,3 | 1645 | 10,8 | 37,0 | 31,9 | 1404 | 8,3 | 31,5 |
5 | 38,0 | 675 | 2,1 | 42,5 | 34,9 | 1540 | 9,6 | 39,5 | 29,5 | 1298 | 7,2 | 34,0 |
10 | 35,5 | 632 | 1,8 | 45,0 | 32,5 | 1433 | 8,4 | 42,0 | 27,1 | 1191 | 6,2 | 36,5 |
15 | 33,1 | 588 | 1,6 | 47,5 | 30,0 | 1326 | 7,3 | 44,5 | 26,6 | 1083 | 5,2 | 39,0 |
20 | 30,6 | 543 | 1,4 | 50,0 | 27,6 | 1217 | 6,2 | 47,0 | 22,2 | 974 | 4,3 | 41,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 38,6 | 1687 | 12,0 | 13,5 | 33,2 | 1447 | 9,4 | 8,0 | 32,7 | 2841 | 32,5 | 7,5 |
-20 | 36,2 | 1583 | 10,7 | 16,0 | 30,8 | 1343 | 8,2 | 10,5 | 30,3 | 2633 | 28,3 | 10,0 |
-15 | 33,8 | 1479 | 9,5 | 18,5 | 28,4 | 1238 | 7,1 | 13,0 | 27,9 | 2424 | 24,4 | 12,5 |
-10 | 31,4 | 1374 | 8,3 | 21,0 | 26,0 | 1133 | 6,1 | 16,0 | 25,4 | 2213 | 20,7 | 15,0 |
-5 | 29,0 | 1268 | 7,2 | 23,5 | 23,6 | 1027 | 5,1 | 18,5 | 23,0 | 2003 | 17,2 | 18,0 |
0 | 26,6 | 1163 | 6,1 | 26,0 | 21,1 | 921 | 4,2 | 21,0 | 20,6 | 1791 | 14,1 | 20,5 |
5 | 24,1 | 1056 | 5,2 | 29,0 | 18,7 | 813 | 3,4 | 23,5 | 18,1 | 1578 | 11,2 | 23,0 |
10 | 21,7 | 948 | 4,3 | 31,5 | 16,2 | 704 | 2,6 | 26,0 | 15,7 | 1364 | 8,6 | 25,5 |
15 | 19,2 | 840 | 3,4 | 34,0 | 13,6 | 593 | 1,9 | 28,5 | 13,2 | 1148 | 6,4 | 28,0 |
20 | 16,7 | 729 | 2,7 | 36,5 | 11,0 | 479 | 1,3 | 30,5 | 10,7 | 930 | 4,4 | 30,5 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 65 + KM L | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 1000 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 35,4 | 629 | 1,3 | 80,5 | 31,2 | 1379 | 5,6 | 68,0 | 28,1 | 1234 | 4,7 | 58,5 |
-20 | 33,9 | 603 | 1,2 | 81,0 | 29,8 | 1314 | 5,1 | 68,5 | 26,6 | 1170 | 4,3 | 59,5 |
-15 | 32,4 | 576 | 1,1 | 81,5 | 28,3 | 1250 | 4,7 | 69,0 | 25,2 | 1106 | 3,9 | 60,0 |
-10 | 30,9 | 549 | 1,0 | 81,5 | 26,9 | 1186 | 4,2 | 70,0 | 23,7 | 1042 | 3,5 | 60,5 |
-5 | 29,4 | 523 | 0,9 | 82,0 | 25,4 | 1122 | 3,8 | 70,5 | 22,2 | 977 | 3,1 | 61,0 |
0 | 27,9 | 496 | 0,9 | 82,5 | 24,0 | 1058 | 3,5 | 71,0 | 20,1 | 913 | 2,7 | 61,5 |
5 | 26,4 | 469 | 0,8 | 83,0 | 22,5 | 994 | 3,1 | 71,5 | 19,3 | 849 | 2,4 | 62,0 |
10 | 24,9 | 442 | 0,7 | 83,0 | 21,1 | 929 | 2,7 | 72,0 | 17,8 | 784 | 2,1 | 62,5 |
15 | 23,3 | 414 | 0,6 | 83,0 | 19,6 | 864 | 2,4 | 72,5 | 16,3 | 718 | 1,8 | 63,0 |
20 | 21,7 | 386 | 0,6 | 83,5 | 18,1 | 799 | 2,1 | 73,0 | 14,8 | 651 | 1,5 | 63,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 24,9 | 1091 | 3,9 | 49,0 | 21,7 | 946 | 3,1 | 39,5 | 20,5 | 1785 | 9,9 | 36,0 |
-20 | 23,5 | 1026 | 3,5 | 50,0 | 20,2 | 881 | 2,8 | 40,0 | 19,0 | 1658 | 8,7 | 36,5 |
-15 | 22,0 | 962 | 3,1 | 50,5 | 18,7 | 816 | 2,4 | 40,5 | 17,6 | 1531 | 7,6 | 37,0 |
-10 | 20,5 | 897 | 2,8 | 51,0 | 17,2 | 751 | 2,1 | 41,0 | 16,1 | 1403 | 6,5 | 38,0 |
-5 | 19,0 | 833 | 2,4 | 51,5 | 15,7 | 686 | 1,8 | 41,5 | 14,7 | 1276 | 5,5 | 38,5 |
0 | 17,6 | 768 | 2,1 | 52,0 | 14,2 | 619 | 1,5 | 42,0 | 13,2 | 1148 | 4,5 | 39,0 |
5 | 16,1 | 703 | 1,8 | 52,5 | 12,7 | 552 | 1,2 | 42,5 | 11,7 | 1019 | 3,7 | 39,5 |
10 | 14,5 | 636 | 1,5 | 53,0 | 11,1 | 483 | 1,0 | 42,5 | 10,2 | 888 | 2,9 | 40,0 |
15 | 13,0 | 569 | 1,2 | 53,0 | 9,5 | 411 | 0,7 | 43,0 | 8,7 | 756 | 2,2 | 40,5 |
20 | 11,4 | 500 | 1,0 | 53,5 | 7,7 | 334 | 0,5 | 42,5 | 7,1 | 621 | 1,5 | 40,5 |
V = 1750 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 54,3 | 965 | 2,8 | 67,5 | 48,6 | 2146 | 12,4 | 58,0 | 43,6 | 1918 | 10,4 | 49,5 |
-20 | 52,0 | 924 | 2,6 | 68,5 | 46,3 | 2045 | 11,3 | 59,0 | 41,4 | 1817 | 9,4 | 50,5 |
-15 | 49,6 | 882 | 2,4 | 69,5 | 44,1 | 1944 | 10,3 | 60,0 | 39,1 | 1716 | 8,5 | 51,5 |
-10 | 47,3 | 841 | 2,2 | 70,0 | 41,8 | 1843 | 9,4 | 61,0 | 36,8 | 1615 | 7,6 | 52,5 |
-5 | 44,9 | 799 | 2,0 | 71,0 | 39,5 | 1742 | 8,5 | 62,0 | 34,5 | 1514 | 6,8 | 53,5 |
0 | 42,6 | 757 | 1,8 | 72,0 | 37,2 | 1642 | 7,6 | 63,0 | 32,2 | 1413 | 6 | 54,5 |
5 | 40,3 | 716 | 1,6 | 73,0 | 34,9 | 1541 | 6,8 | 64,0 | 29,9 | 1312 | 5,2 | 55,5 |
10 | 37,9 | 672 | 1,5 | 73,5 | 32,6 | 1439 | 6,0 | 65,0 | 27,5 | 1210 | 4,5 | 56,5 |
15 | 35,4 | 630 | 1,3 | 74,5 | 30,3 | 1337 | 5,3 | 66,0 | 25,2 | 1106 | 3,9 | 57,0 |
20 | 33,0 | 586 | 1,2 | 75,0 | 27,9 | 1233 | 4,5 | 66,5 | 22,8 | 1002 | 3,2 | 57,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 38,6 | 1690 | 8,5 | 41,0 | 33,6 | 1463 | 6,8 | 32,0 | 32,0 | 2785 | 22,2 | 29,5 |
-20 | 36,3 | 1590 | 7,7 | 42,0 | 31,2 | 1362 | 6,0 | 33,0 | 29,7 | 2585 | 19,4 | 30,5 |
-15 | 34,0 | 1489 | 6,8 | 43,0 | 28,9 | 1260 | 5,2 | 34,0 | 27,4 | 2385 | 16,8 | 31,5 |
-10 | 31,7 | 1387 | 6,0 | 44,0 | 26,6 | 1159 | 4,5 | 35,0 | 25,1 | 2184 | 14,3 | 32,5 |
-5 | 29,4 | 1286 | 5,2 | 45,0 | 24,2 | 1056 | 3,8 | 36,0 | 22,8 | 1983 | 12,0 | 33,5 |
0 | 27,1 | 1185 | 4,5 | 46,0 | 21,9 | 953 | 3,2 | 37,0 | 20,5 | 1782 | 9,9 | 34,5 |
5 | 24,7 | 1082 | 3,8 | 47,0 | 19,5 | 849 | 2,6 | 38,0 | 18,2 | 1580 | 8,0 | 35,5 |
10 | 22,4 | 979 | 3,2 | 47,5 | 17,1 | 743 | 2,1 | 38,5 | 15,8 | 1750 | 6,3 | 36,5 |
15 | 20,0 | 874 | 2,6 | 48,5 | 14,6 | 634 | 1,6 | 39,5 | 13,4 | 1167 | 4,7 | 37,5 |
20 | 17,5 | 767 | 2,1 | 49,5 | 12,0 | 521 | 1,1 | 40,0 | 11,0 | 957 | 3,3 | 38,5 |
V = 2800 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 75,6 | 1345 | 5,1 | 55,5 | 68,6 | 3026 | 23,1 | 48,0 | 61,5 | 2700 | 19,3 | 40,5 |
-20 | 72,4 | 1286 | 4,7 | 57,0 | 65,3 | 2883 | 21,2 | 49,5 | 58,2 | 2557 | 17,5 | 42,0 |
-15 | 69,1 | 1228 | 4,3 | 58,5 | 62,1 | 2739 | 19,3 | 51,0 | 54,9 | 2414 | 15,8 | 43,5 |
-10 | 65,8 | 1169 | 4,0 | 60,0 | 58,8 | 2596 | 17,5 | 52,5 | 51,7 | 2271 | 14,1 | 45,0 |
-5 | 62,5 | 1110 | 3,6 | 61,0 | 55,6 | 2453 | 15,8 | 54,0 | 48,4 | 2127 | 12,5 | 46,5 |
0 | 59,2 | 1052 | 3,3 | 62,5 | 52,0 | 2310 | 14,1 | 55,5 | 45,2 | 1984 | 11,0 | 47,5 |
5 | 55,8 | 993 | 2,9 | 64,0 | 49,1 | 2166 | 12,6 | 56,5 | 41,9 | 1840 | 9,6 | 49,0 |
10 | 52,5 | 933 | 2,6 | 65,0 | 45,8 | 2021 | 11,1 | 58,0 | 38,6 | 1694 | 8,3 | 50,5 |
15 | 49,1 | 872 | 2,3 | 66,5 | 42,5 | 1875 | 9,7 | 59,5 | 35,2 | 1547 | 7,1 | 52,0 |
20 | 45,6 | 810 | 2,0 | 67,5 | 39,2 | 1728 | 8,4 | 61,0 | 31,8 | 1399 | 5,9 | 53,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 54,3 | 2376 | 15,8 | 33,0 | 47,1 | 2052 | 12,6 | 25,0 | (2) | |||
-20 | 51,0 | 2233 | 14,1 | 34,5 | 43,8 | 1909 | 11,0 | 26,5 | 42,0 | 3651 | 36,3 | 24,5 |
-15 | 47,8 | 2090 | 12,5 | 36,0 | 40,5 | 1766 | 9,6 | 28,0 | 38,7 | 3366 | 31,3 | 26,0 |
-10 | 44,5 | 1946 | 11,0 | 37,0 | 37,2 | 1622 | 8,2 | 29,5 | 35,4 | 3081 | 26,7 | 27,5 |
-5 | 41,2 | 1803 | 9,6 | 38,5 | 33,9 | 1477 | 7,0 | 31,0 | 32,1 | 2795 | 22,4 | 29,0 |
0 | 37,9 | 1659 | 8,3 | 40,0 | 30,6 | 1331 | 5,8 | 32,5 | 28,8 | 2509 | 18,4 | 30,5 |
5 | 34,6 | 1514 | 7,0 | 41,5 | 27,2 | 1185 | 4,7 | 33,5 | 25,5 | 2221 | 14,8 | 32,0 |
10 | 31,2 | 1367 | 5,8 | 43,0 | 23,8 | 1035 | 3,7 | 35,0 | 22,2 | 1929 | 11,5 | 33,0 |
15 | 27,8 | 1218 | 4,7 | 44,0 | 20,3 | 883 | 2,8 | 36,5 | 18,8 | 1635 | 8,5 | 34,5 |
20 | 24,4 | 1068 | 3,8 | 45,5 | 16,7 | 726 | 2,0 | 37,5 | 15,8 | 1337 | 6,0 | 36,0 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
LEO FB 95 + KM 95 | ||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
V = 2650 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 67,9 | 1206 | 3,6 | 51,5 | 62,4 | 2753 | 16,6 | 45,0 | 55,9 | 2455 | 13,9 | 38,0 |
-20 | 64,9 | 1153 | 3,3 | 53,0 | 59,4 | 2622 | 15,2 | 47,0 | 52,9 | 2324 | 12,6 | 39,5 |
-15 | 61,9 | 1100 | 3,0 | 54,5 | 56,4 | 2490 | 13,8 | 48,5 | 49,9 | 2193 | 11,3 | 41,0 |
-10 | 58,9 | 1046 | 2,8 | 56,0 | 53,5 | 2359 | 12,5 | 50,0 | 46,9 | 2062 | 10,1 | 42,5 |
-5 | 55,9 | 993 | 2,5 | 57,5 | 50,5 | 2227 | 11,3 | 51,5 | 43,9 | 1930 | 9,0 | 44,0 |
0 | 52,9 | 940 | 2,3 | 59,0 | 47,5 | 2096 | 10,1 | 53,0 | 40,9 | 1799 | 7,9 | 45,5 |
5 | 49,9 | 886 | 2,1 | 60,5 | 44,5 | 1965 | 9,0 | 54,5 | 37,9 | 1667 | 6,9 | 47,5 |
10 | 46,8 | 832 | 1,8 | 62,0 | 41,5 | 1832 | 7,9 | 56,0 | 34,9 | 1533 | 5,9 | 49,0 |
15 | 43,7 | 777 | 1,6 | 63,5 | 38,5 | 1698 | 6,9 | 57,5 | 31,8 | 1399 | 5,0 | 50,5 |
20 | 40,6 | 721 | 1,4 | 65,0 | 35,4 | 1563 | 5,9 | 59,0 | 28,8 | 1263 | 4,2 | 52,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 49,4 | 2160 | 11,3 | 30,5 | 42,8 | 1865 | 9,0 | 23,0 | 41,4 | 3599 | 30,2 | 21,5 |
-20 | 46,4 | 2029 | 10,1 | 32,0 | 39,8 | 1734 | 7,9 | 24,5 | 38,4 | 3339 | 26,3 | 23,0 |
-15 | 43,4 | 1898 | 9,0 | 33,5 | 36,8 | 1603 | 6,9 | 26,5 | 35,4 | 3077 | 22,7 | 25,0 |
-10 | 40,4 | 1766 | 7,9 | 35,5 | 33,8 | 1471 | 5,9 | 28,0 | 32,4 | 2815 | 19,3 | 26,0 |
-5 | 37,4 | 1635 | 6,9 | 37,0 | 30,7 | 1339 | 5,0 | 29,5 | 27,9 | 2553 | 16,2 | 28,0 |
0 | 34,3 | 1503 | 5,9 | 38,5 | 27,7 | 1206 | 4,1 | 31,0 | 26,3 | 2289 | 13,3 | 29,5 |
5 | 31,3 | 1370 | 5,0 | 40,0 | 24,6 | 1073 | 3,4 | 32,5 | 23,3 | 2025 | 10,7 | 31,0 |
10 | 28,3 | 1236 | 4,2 | 41,5 | 21,5 | 937 | 2,6 | 34,0 | 20,2 | 1759 | 8,3 | 32,5 |
15 | 25,2 | 1100 | 3,4 | 43,0 | 18,3 | 798 | 2,0 | 35,5 | 17,2 | 1492 | 6,2 | 34,0 |
20 | 22,0 | 963 | 2,7 | 44,5 | 15,1 | 658 | 1,4 | 36,5 | 14,0 | 1222 | 4,3 | 35,5 |
V = 4420 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 96,4 | 1713 | 6,7 | 40,0 | 89,0 | 3928 | 31,8 | 35,0 | 79,7 | 3501 | 26,5 | 28,5 |
-20 | 92,1 | 1638 | 6,2 | 42,0 | 84,8 | 3741 | 29,1 | 37,0 | 75,4 | 3315 | 24,0 | 31,0 |
-15 | 87,9 | 1562 | 5,7 | 44,0 | 80,5 | 3554 | 26,5 | 39,0 | 71,2 | 3128 | 21,5 | 33,0 |
-10 | 83,6 | 1486 | 5,2 | 46,0 | 76,3 | 3366 | 24,0 | 41,5 | 66,9 | 2940 | 19,3 | 35,0 |
-5 | 79,3 | 1410 | 4,7 | 48,5 | 72,0 | 3179 | 21,6 | 43,5 | 62,6 | 2752 | 17,1 | 37,0 |
0 | 75,1 | 1334 | 4,3 | 50,5 | 67,8 | 2991 | 19,3 | 45,5 | 58,4 | 2565 | 15,0 | 39,0 |
5 | 70,8 | 1258 | 3,8 | 52,5 | 63,5 | 2803 | 17,2 | 47,5 | 54,1 | 2376 | 13,1 | 41,0 |
10 | 66,4 | 1180 | 3,4 | 54,0 | 59,2 | 2613 | 15,1 | 49,5 | 49,7 | 2185 | 11,2 | 43,0 |
15 | 62,0 | 1102 | 3,0 | 56,0 | 54,9 | 2421 | 13,1 | 51,5 | 45,4 | 1993 | 9,5 | 45,0 |
20 | 57,6 | 1023 | 2,7 | 58,0 | 50,5 | 2228 | 11,3 | 53,5 | 40,9 | 1799 | 7,9 | 47,0 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 70,3 | 3078 | 21,6 | 22,5 | 60,9 | 2656 | 17,1 | 16,0 | (2) | |||
-20 | 66,1 | 2892 | 19,3 | 24,5 | 56,7 | 2470 | 15,0 | 18,0 | ||||
-15 | 61,8 | 2705 | 17,1 | 26,5 | 52,4 | 2283 | 13,0 | 20,5 | 50,5 | 4395 | 43,3 | 19,0 |
-10 | 57,5 | 2517 | 15,0 | 28,5 | 48,1 | 2095 | 11,1 | 22,5 | 46,2 | 4020 | 36,9 | 21,0 |
-5 | 53,2 | 2329 | 13,0 | 30,5 | 43,7 | 1907 | 9,4 | 24,5 | 41,9 | 3645 | 30,9 | 23,0 |
0 | 48,9 | 2141 | 11,2 | 32,8 | 39,4 | 1717 | 7,8 | 26,5 | 37,6 | 3268 | 25,3 | 25,0 |
5 | 44,6 | 1951 | 9,4 | 35,0 | 35,0 | 1526 | 6,3 | 28,5 | 33,2 | 2889 | 20,3 | 27,0 |
10 | 40,2 | 1759 | 7,8 | 37,0 | 30,6 | 1333 | 4,9 | 30,5 | 28,8 | 2509 | 15,7 | 29,0 |
15 | 35,8 | 1566 | 6,4 | 39,0 | 26,1 | 1136 | 3,7 | 32,5 | 24,4 | 2126 | 11,6 | 31,0 |
20 | 31,3 | 1370 | 5,0 | 40,5 | 21,5 | 936 | 2,6 | 34,0 | 20,0 | 1740 | 8,1 | 33,0 |
V = 6500 m3/h | ||||||||||||
Tw1/Tw2 = 120/70°C | Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | ||||||||||
-25 | 123,3 | 2193 | 10,5 | 31,5 | (2) | 102,3 | 4494 | 41,9 | 22,0 | |||
-20 | 117,9 | 2096 | 9,7 | 34,0 | 108,9 | 4804 | 46,1 | 30,0 | 96,8 | 4255 | 37,9 | 24,5 |
-15 | 112,5 | 1999 | 8,9 | 36,5 | 103,4 | 4564 | 42,0 | 32,5 | 91,4 | 4015 | 34,0 | 27,0 |
-10 | 107,0 | 1902 | 8,1 | 39,0 | 98,0 | 4323 | 38,0 | 35,0 | 85,9 | 3774 | 30,4 | 29,5 |
-5 | 101,5 | 1804 | 7,4 | 41,5 | 92,5 | 4082 | 34,2 | 37,0 | 80,4 | 3533 | 26,7 | 31,5 |
0 | 96,0 | 1707 | 6,7 | 43,5 | 87,0 | 3841 | 30,5 | 39,5 | 74,9 | 3291 | 23,7 | 34,0 |
5 | 90,5 | 1609 | 6,0 | 46,0 | 81,5 | 3599 | 27,1 | 42,0 | 69,4 | 3049 | 20,6 | 36,5 |
10 | 84,9 | 1509 | 5,3 | 48,5 | 76,0 | 3354 | 23,8 | 44,5 | 63,8 | 2803 | 17,6 | 39,0 |
15 | 79,3 | 1409 | 4,7 | 51,0 | 70,4 | 3107 | 20,7 | 47,0 | 58,2 | 2556 | 14,9 | 41,5 |
20 | 73,5 | 1307 | 4,1 | 53,0 | 64,8 | 2858 | 17,8 | 49,0 | 52,5 | 2306 | 12,4 | 43,5 |
Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||
-25 | 90,3 | 3950 | 34,0 | 16,5 | 78,2 | 3407 | 26,8 | 11,0 | (2) | |||
-20 | 84,8 | 3711 | 30,3 | 19,0 | 72,7 | 3168 | 23,5 | 13,5 | ||||
-15 | 79,3 | 3470 | 26,8 | 21,5 | 67,2 | 2928 | 20,4 | 16,0 | ||||
-10 | 73,8 | 3229 | 23,5 | 24,0 | 61,6 | 2687 | 17,4 | 18,0 | ||||
-5 | 68,3 | 2988 | 20,4 | 26,0 | 56,1 | 2444 | 14,7 | 20,5 | ||||
0 | 62,7 | 2745 | 17,5 | 28,5 | 50,5 | 2201 | 12,2 | 23,0 | 48,3 | 4198 | 39,9 | 22,0 |
5 | 57,2 | 2502 | 14,8 | 31,0 | 44,9 | 1956 | 9,8 | 25,5 | 42,7 | 3711 | 31,9 | 24,5 |
10 | 51,5 | 2255 | 12,3 | 33,5 | 39,2 | 1707 | 7,7 | 28,0 | 37,0 | 3221 | 22,8 | 27,0 |
15 | 45,9 | 2006 | 9,9 | 35,5 | 33,4 | 1455 | 5,8 | 30,0 | 31,4 | 2728 | 18,2 | 29,0 |
20 | 40,1 | 1755 | 7,8 | 38,0 | 27,5 | 1199 | 4,1 | 32,5 | 25,6 | 2230 | 12,7 | 31,5 |
In order to get parameters of devices operating with mediums at different temperature please contact our sales department
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
(2) Not allowed, too low temperature at the outlet of the devices
The heating and ventilation units LEO KM L + LEO FB can be installed on the walls or under the ceiling in any position. The basic equipment of the unit consists of the brackets for installation under the ceiling using pins.
The additional elements for installation of LEO KM L + LEO FB are:
Installation brackets – enable installation on vertical partitions.
Flexible adapter – ensures easy installation of the unit to the air intake or further duct installation and prevents possible vibration.
We present also some installation tips below:
Steady air circulation should be provided in the entire room.
It is not recommended to supply the fresh air by ducts with may cause additional local pressure losses. It may cause a significant decrease of efficiency.
It is allowed to supply the fresh air to the unit by straight ducts.
Big objects must not limit the air stream of the heater.
Heaters installed on the opposite walls should be overlapped.
Heaters should be installed in a way that ensures free air supply
around the unit.